Download document () of 20
Hydraulic-Magnetic Circuit Breaker (HMCB)

AR Series

Ultra-high interrupting hydraulic-magnetic circuit breaker for single or multipole applications. The AR series delivers significant performance advantages in a compact package. Suitable for branch circuit protection, the AR can be used in a wide variety of applications, including lighting and power distribution equipment.

Featured applications: Telecom, rail, defense, medical

Series Features

  • Suitable for AC and DC applications
  • Maintains 100 % rating capability regardless of ambient temperature
  • Rating from 0.02 to 100 A
  • Voltage up to 125 VDC, 480 VAC
  • Maximum interrupting capacity up to 10'000 A
  • Up to 6 poles
  • Suitable for 400 Hz electrical systems
  • Compact and lightweight design
  • Customizable handles, including illuminated toggle
  • Variety of terminals
  • Optional auxiliary switches (single, double, protected or not)
  • Optional Mid-Trip feature (with or without Alarm switch)
  • Optional double switch redundancy setup (with DPDT switch)
  • Easy panel mounting
  • Compatible with Remote Breaker Reset (RBR) series

 

HMCB Features

All Eaton Heinemann HMCBs have the following features:

  • Large operating temperature range of -40 °C to 85 °C without derating
  • High inrush tolerance
  • Resistance to shocks and vibrations
  • Resistance to humidity and corrosion
  • Immediate resetting after trip
  • Multiple industry and quality certifications

 

HMCB Benefits

  • Extreme temperature protection: Operates reliably from -40 °C to +85 °C, maintaining constant trip ratings and protecting cables and equipment without the need for costly oversizing.
  • Stable rating: Maintains 100 % rating capability regardless of ambient temperature.
  • Precision tripping: Ideal for applications with sensitive equipment requiring precise tripping point protection.
  • Robust Design: Build to last, even in the harshest of environments, reducing maintenance or replacement costs.
  • Minimal Voltage Drop: Lower internal resistance compared to Thermal-magnetic circuit breakers, ideal for low voltage DC applications.
  • Avoid Nuisance Tripping: Shock-resistant and reduces EMC/EMI noise micro-cuts.
  • Harsh Environment Protection: Resistant to humidity and saline environments.
  • Hot-Pluggable Design: Allows maintenance without shutting down the entire system.
  • Integrated auxiliary alarm switch: Saves horizontal space and cost by eliminating the need for extra poles.
Specifications

Electrical characteristics

Maximum number of poles 6
Rating

DC: 0.02 – 100 A

AC: 0.02 – 100 A

Voltage range

DC: up to 125 VDC

AC: up to 480 VAC

Breaker ratings

UL rating

80 VDC: 100 A

125 VDC: 50 A

250 V 50/60/400 Hz: 100 A

277 V 50/60 Hz: 50 A

415 V 50/60 Hz: 50 A

480 V 50/60 Hz: 30 A

DIN EN rating

DC: 100 A

50/60 Hz: 100 A

Interrupting capacity

UL rating

80 VDC: 7.5 kA

125 VDC: 5 kA

250 V 50/60 Hz: 5 kA

277 V 50/60 Hz: 5 kA

415 V 50/60 Hz: 5 kA

480 V 50/60 Hz: 3 kA

DIN rating 

DC: 10kA

50/60Hz: 5kA

Dielectric strength 3’750 VAC 50/60 Hz
Insulation resistance 100 MOhm at 500 VDC

Trip specification

Trip options                                                                                         Series, shunt, relay, remote trip off (Ducon), switch
Trip delay Instantaneous, short, medium, long delay
High inrush

50 Hz: 8x, 15x, 22x In

60 Hz: 10x, 18x, 25x In

Operating conditions

Operating temperature                        -40°C to +85°C (-40°F to +185°F)
Auxiliary contacts SPDT, DPDT, protected or not protected
Mid trip, with or without Alarm switch Optional

Certifications and Approvals

Shock                                                         IEC 60068-2-27, MIL-STD-202 method 213
Vibration IEC 60068-2-6, MIL-STD-202 method 204
Humidity IEC 60068-2-78, MIL-STD-202 method 103
UL/CSA Approvals UL1077, UL489, UL489A, CSA C 22.2
Other approvals DIN EN 60934/60947-2, CCC
Approvals – Rail

EN-45545, NFF, IEC, ASTM, Bombardier

SMP, Boeing BSS, SNCF

Dimensions

Poles                                                     1-6 poles
Dimensions WxHxD (per pole) 19 x 63.5 x 67 mm (0.75” x 2.5” x 2.6”)
Weight per pole 95 grams (0.21 lb)

Mounting, Handle, Terminals

Mounting styles                                              Front, Snap-in
Handle Toggle, illuminated toggle, rocker, flat rocker
Power terminals Bullet, stud, fuse, or screw terminals
Power connection Rear