Download document () of 20

ADS Series

The ADS series hydraulic-magnetic circuit breaker effortlessly snaps onto a standard 35 mm DIN rail, significantly reducing installation time. With a wide range of available accessories, the ADS series is the ideal alternative to DIN rail-mounted fuse blocks.

Featured applications: Rail, machine building

Series Features

  • Suitable for AC and DC applications
  • Maintains 100 % rating capability regardless of ambient temperature
  • Rating from 0.1 to 63 A
  • Voltage up to 80 VDC, 480 VAC
  • Maximum interrupting capacity up to 5'000 A
  • Up to 4 poles
  • Small and lightweight
  • Designed for DIN rail mounting
  • Includes integrated release coil
  • Available with Ring Tong for the rail industry
  • Integrated SPST auxiliary switch
  • Optional Mid-Trip feature

 

HMCB Features

All Eaton Heinemann HMCBs have the following features:

  • Large operating temperature range of -40 °C to 85 °C without derating
  • High inrush tolerance
  • Resistance to shocks and vibrations
  • Resistance to humidity and corrosion
  • Immediate resetting after trip
  • Multiple industry and quality certifications

 

HMCB Benefits

  • Extreme temperature protection: Operates reliably from -40 °C to +85 °C, maintaining constant trip ratings and protecting cables and equipment without the need for costly oversizing.
  • Stable rating: Maintains 100 % rating capability regardless of ambient temperature.
  • Precision tripping: Ideal for applications with sensitive equipment requiring precise tripping point protection.
  • Robust Design: Build to last, even in the harshest of environments, reducing maintenance or replacement costs.
  • Minimal Voltage Drop: Lower internal resistance compared to Thermal-magnetic circuit breakers, ideal for low voltage DC applications.
  • Avoid Nuisance Tripping: Shock-resistant and reduces EMC/EMI noise micro-cuts.
  • Harsh Environment Protection: Resistant to humidity and saline environments.
  • Hot-Pluggable Design: Allows maintenance without shutting down the entire system.
  • Integrated auxiliary alarm switch: Saves horizontal space and cost by eliminating the need for extra poles.
Specifications

Electrical characteristics

Maximum number of poles

4

Rating

DC: 0.1 – 63 A

AC: 0.1 – 63 A

Voltage range

DC: up to 80 VDC

AC: up to 480 VAC

Breaker ratings

UL rating

80 VDC: 63 A

400V 50/60 Hz: 63 A   
      

DIN EN rating

80 VDC: 0.1 – 63 A

Interrupting capacity

UL rating

80 VDC: 5 kA 

250 V 50/60 Hz: 5 kA 

480 V 50/60 Hz: 3 kA
 

DIN rating

80 VDC: 3 kA

Dielectric strength

3’750 VAC 50/60 Hz

Insulation resistance

100 MOhm at 500 VDC

Trip specification

Trip options

Series, remote trip off (Ducon), relay, switch

Trip delay

Instantaneous, short, medium, long delay, motor start

High inrush

50 Hz: 8x, 15x, 22x In

60 Hz: 10x, 18x, 25x In

Operating conditions

Operating temperature

-40 °C to +85 °C (-40 °F to +185 °F)

Auxiliary contacts

SPST

Mid trip

Optional

Certifications and Approvals

Shock

IEC 60068-2-27, MIL-STD-202 method 213

Vibration

IEC 60068-2-6, MIL-STD-202 method 204

Humidity

IEC 60068-2-78, MIL-STD-202 method 103

UL/CSA Approvals

UL1077, CSA C 22.2

Other approvals

DIN EN 60947-2, CCC

Approvals – Rail

EN-45545, NFF, IEC, ASTM, Bombardier SMP, Boeing BSS, SNCF

Dimensions

Poles

1-4 poles

Dimensions WxHxD (per pole)

19 x 105 x 73 mm (0.75” x 4.10” x 2.90”)

Weight per pole

145 grams (0.32 lb)

Mounting, Handle, Terminals

Mounting styles

35 mm DIN rail

Handle

Toggle

Power terminals

Pressure wire terminal

Power connection

Top and bottom
Download Links